본문 바로가기

Sanitary Temperature Sensor

R231, R232_Sanitary resistance temperature detector

R231 single element R232 double element

Service intended

Sanitary RTDs can measure temperature from -50 to 200 °C. These sensors are available in Tri-clamp design with the immersion length from 50 to 250 mm. The wetted part of this assembly is polished to exceed No.4 minimum finish which is required by 3-A sanitary council standard #74-06.

Element Pt 100 Ω at 0 ℃
TCR : 3,850 ppm/k
Tolerances on temperature reading Class A : ± (0.15 + 0.002 l t l)
Class B : ± (0.3 + 0.005 l t l)
* t : Reading temperature (℃)
Element and lead wire configurations Single element : 2, 3 and 4 wire
Double element : 4 and 6 wire

Standard features

Head type Weatherproof (ALDC)
Weatherproof (304SS)
Stem material 304SS, 316SS, 316L SS
Process connection Tri - clamp connection
1, 1½ and 2S

© WISE Control Inc. All rights reserved. ALL PRODUCT, PRODUCT SPECIFICATIONS AND DATA ARE SUBJECT TO CHANGE WITHOUT NOTICE TO IMPROVE RELIABILITY, FUNCTION OR DESIGN OR OTHERWISE.